• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL 3) to IEC/EN 61508 and IEC/EN 61511
• Output: 3 NO or 2 NO, 1 NC instantaneous contacts and
3 NO release delayed contacts
• Single and 2-channel operation
• Line fault detection on On-button,
when On-button is connected to S33-S34
• Manual restart with button on S33-S34 or automatic restart with
bridge between S13-S14
• With or without cross fault monitoring in the E-stop loop
• LED indication for supply, channel 1/2 and release delayed contacts
• Removable terminal strips
• Wire connection: also 2 x 1.5 mm2 stranded ferruled (isolated),
DIN 46 228-1/-2/-3/-4 or
2 x 2.5 mm2 stranded ferruled DIN 46 228-1/-2/-3
• Width
BH 5928: 45 mm
BI 5928: 67.5 mm
• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL 3) to IEC/EN 61508 and IEC/EN 61511
• Output: 3 NO or 2 NO, 1 NC instantaneous contacts and
3...
Function | Emergency stop module with time delay |
Also suited as safety gate monitor | + |
Cat. / PL according to EN ISO 13849-1 | 4/e |
SIL CL according to IEC/EN 62061 | 3 |
1- / 2-channel | 1; 2 |
Output contacts max. | 3 s; 3 sv |
Thermal current Ith max. | 5 A |
Cross fault detection | + |
Nominal voltage DC | + |
Connection | PS |
Width | 67,5 mm |
Type | BI 5928 |
Please select required language:
Datasheet / Operating Instructions, File: pdf, File size 3 MB